Navien Air Conditioner: Compressor discharge temperature protection (T5)
Compressor discharge temperature protection (T5) on a Navien air conditioner: If compressor discharge temperature T5 goes above its set maximum, the unit stops until T5 reaches the recovery temperature of 194 F (90 C). The unit restarts when T5 is below the recovery temperature of 194 F (90 C). The manual does not print the numeric set maximum on this page.
Applies to: NAA outdoor unit
Common causes of compressor discharge temperature protection (t5)
- High discharge temperature, possibly from low refrigerant charge, restriction, or low superheat
How to fix compressor discharge temperature protection (t5): step by step
- Check T5 reading on the parameter check table.
- Check refrigerant charge and superheat readings.
- Restart is automatic once T5 falls to the recovery point.
If the unit shows an error code, look it up: Navien Air Conditioner codes
Source: Navien NAA air conditioner service manual, p. 17. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.