Updated · by Aurora Star Tech Inc.

Wire circulation pumps to P1 and P2 by priority on a Viessmann boiler: P1 and P2 have priority rules for DHW, heating circuit and recirculation pumps.

Homeowner with a boiler problem? Call (647) 657-2977 or book a service call — licensed technicians across Vaughan and the GTA.

Applies to: P1 and P2 plugs

How to fix wire circulation pumps to p1 and p2 by priority: step by step

  1. P1: connect DHW pump first; if no DHW pump, use heating circuit pump for circuit without mixing valve.
  2. P2: connect heating circuit pump for circuit without mixing valve or circuits with mixing valve first.
  3. If no heating circuit A1 pump, connect DHW recirculation pump to P2.
  4. If a heating circuit pump without mixing valve is used, connect the DHW recirculation pump to the P1 extension (accessories).
  5. Connect standalone DHW recirculation pumps externally.
Safety: Gas, electrical and refrigerant work must be done by a licensed technician. Turn off power and gas before servicing, never bypass a safety control, and always follow the manufacturer's manual for your exact model.

If the unit shows an error code, look it up: Viessmann Boiler codes

Models

399500750100015002000CI2 399CI2 399/500CI2 500CI2 750CI2 750/1000CI2 1000CI2 1500CI2 1500/2000CI2 2000Vitocrossal 200 CI2 399Vitocrossal 200 CI2 500Vitocrossal 200 CI2 750Vitocrossal 200 CI2 1000Vitocrossal 200 CI2 1500Vitocrossal 200 CI2 2000

Source: Vitocrossal 200 CI2 Installation Instructions, p. 26. Written in our own words as a summary; always check the original manual.

General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.

Emergency Boiler Repair

647-657-2977