Updated · by Aurora Star Tech Inc.

Waterside flow and low-loss header on a Viessmann boiler: The boiler is for closed loop, forced circulation hot water systems only. Size pipe using the standard friction loss method and stay within the boiler minimum and maximum flow rates. Max flow is 14.3 GPM (3,250 L/h). If system flow exceeds the max, falls below the min, or is unknown, a low-loss header is strongly recommended. Primary-secondary piping with closely spaced tees is an alternative, but a low-loss header is preferred. The built-in low-loss header logic in the boiler maintains the required temperature rise through communication with the header. The temperature rise text in the manual is partly garbled.

Homeowner with a boiler problem? Call (647) 657-2977 or book a service call — licensed technicians across Vaughan and the GTA.

Applies to: Vitodens 200-W B2HB 45, 57, 160, 199

How to fix waterside flow and low-loss header: step by step

  1. Size the piping using the standard friction loss method.
  2. Confirm the system flow is within the boiler limits (min to 14.3 GPM).
  3. If flow is above max, below min, or unknown, install a low-loss header.
  4. Refer to the Technical Data manual for low-loss header information.
  5. Check pressure drop from the primary circuit chart when sizing the circulator.
Safety: Gas, electrical and refrigerant work must be done by a licensed technician. Turn off power and gas before servicing, never bypass a safety control, and always follow the manufacturer's manual for your exact model.

If the unit shows an error code, look it up: Viessmann Boiler codes

Models

Vitodens 200-W B2HB 45Vitodens 200-W B2HB 57Vitodens 200-W B2HB 160Vitodens 200-W B2HB 199

More commissioning tips for boiler

Source: Vitodens 200-W B2HB installation manual, p. 30. Written in our own words as a summary; always check the original manual.

General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.