Viessmann Boiler: Vent termination location requirements – USA
Vent termination location requirements - USA on a Viessmann boiler: Vent must follow local rules plus ANSI Z223.1 or NFPA 54. Flexible vent is only for vertical runs. Key limits: not less than 7 ft (2.13 m) above a paved walk or driveway on public property; 4 ft (1.2 m) horizontally from service regulator vents, electric and gas meters, and relief equipment; 3 ft (0.9 m) above any forced air inlet within 10 ft (3 m); 1 ft (0.3 m) above grade or snow level; 1 ft (0.3 m) from a window, door, or non-mechanical air inlet; 3 ft (0.9 m) from an inside corner of outside walls.
Applies to: Vent termination, USA
How to fix vent termination location requirements - usa: step by step
- Confirm the vent does not end inside any listed clearance.
- Keep the termination away from planters, patios, and windows where flue gas causes fogging.
- Keep flue gas away from brick, siding, or other surfaces that can be damaged by heat or condensate.
- Keep the termination 3 ft (0.9 m) from the property line where possible.
If the unit shows an error code, look it up: Viessmann Boiler codes
Models
399500750100015002000CI2 399CI2 399/500CI2 500CI2 750CI2 750/1000CI2 1000CI2 1500CI2 1500/2000CI2 2000Vitocrossal 200 CI2 399Vitocrossal 200 CI2 500Vitocrossal 200 CI2 750Vitocrossal 200 CI2 1000Vitocrossal 200 CI2 1500Vitocrossal 200 CI2 2000
Source: Vitocrossal 200 CI2 Installation Instructions, p. 51. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.