Warming things up…Dialing in your comfort…Almost cozy…
Reliable Heating and Cooling Solutions – Quality Service, Fair Prices, Guaranteed Satisfaction!

Viessmann Boiler: Vent termination location requirements – Canada

Updated · by Aurora Star Tech Inc.

Vent termination location requirements - Canada on a Viessmann boiler: Vent must follow local rules plus CAN/CSA-B149.1 or .2. Flexible vent is only for vertical runs. Key limits: not less than 7 ft (2.13 m) above a paved walk or driveway on public property; not less than 6 ft (1.83 m) from a mechanical air inlet; not less than 1 ft (0.3 m) above grade or snow level; 1 ft (0.3 m) from a window or door that opens for inputs up to 100,000 Btu/h, and 3 ft (0.9 m) above 100,000 Btu/h; 3 ft (0.9 m) from a gas regulator vent or meter/regulator assembly; not under a veranda, porch, or deck unless open on two sides and more than 1 ft (0.3 m) below it; 3 ft (0.9 m) from an inside corner of outside walls.

Homeowner with a boiler problem? Call (647) 657-2977 or book a service call — licensed technicians across Vaughan and the GTA.

Applies to: Vent termination, Canada

How to fix vent termination location requirements - canada: step by step

  1. Confirm the vent does not end where the clearances above are not met.
  2. Keep the termination away from planters, patios, and windows where flue gas causes fogging.
  3. Keep the termination where flue gas will not hit brick, siding, or other construction, or hot gas will not cause damage or injury.
  4. Keep the termination 3 ft (0.9 m) from the property line where possible.
Safety: Gas, electrical and refrigerant work must be done by a licensed technician. Turn off power and gas before servicing, never bypass a safety control, and always follow the manufacturer's manual for your exact model.

If the unit shows an error code, look it up: Viessmann Boiler codes

Models

399500750100015002000CI2 399CI2 399/500CI2 500CI2 750CI2 750/1000CI2 1000CI2 1500CI2 1500/2000CI2 2000Vitocrossal 200 CI2 399Vitocrossal 200 CI2 500Vitocrossal 200 CI2 750Vitocrossal 200 CI2 1000Vitocrossal 200 CI2 1500Vitocrossal 200 CI2 2000

Source: Vitocrossal 200 CI2 Installation Instructions, p. 51. Written in our own words as a summary; always check the original manual.

General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.

Emergency Boiler Repair

647-657-2977