Viessmann Boiler: Setting the maximum operational burner input
Setting the maximum operational burner input on a Viessmann boiler: Sets the maximum burner output between 0 and 100% of rated input. Observe the modulation range (see p. 16).
Applies to: Vitocrossal 200 CM2 burner control unit
How to fix setting the maximum operational burner input: step by step
- Press S for longer than 2 seconds until the menu item flashes.
- Scroll with Y until 6 shows under Service, then press S. 6 shows under Status.
- Press S. 1 shows under Status and the current maximum output % shows under Service.
- Press Y or B to set the required maximum output.
- Press S to confirm. 1 under Service means applied, 0 means it failed.
- Press S to return to the operating display.
- Press R to reset the unit and apply settings.
If the unit shows an error code, look it up: Viessmann Boiler codes
Models
186246311CM2 186 burnerCM2 246 burnerCM2 311 burnerVitocrossal 200 CM2 186Vitocrossal 200 CM2 246Vitocrossal 200 CM2 311Vitocrossal 200 CM2 400Vitocrossal 200 CM2 500Vitocrossal 200 CM2 620Vitocrossal 200 CM2 620 TX
More settings shortcuts tips for boiler
Source: Vitocrossal 200 CM2 186 to 311 Service Instructions, p. 46. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.