Viessmann Boiler: Set maximum burner output
Set maximum burner output on a Viessmann boiler: Changes the maximum operating output of the burner in percent. Stay inside the modulation range given on page 67.
Applies to: CA3B Series 2.5 to 6.0
How to fix set maximum burner output: step by step
- Hold the S button for more than 2 seconds until the indicator flashes.
- Turn the dial until 6 shows under Service.
- Press S. A 6 shows under Status.
- Press S. A 1 shows under Status and the current maximum output (%) shows under Service.
- Use Y or B to set the required maximum output.
- Press S to confirm. A 1 under Service means success, 0 means it failed.
- Press S to return to the operating display.
If the unit shows an error code, look it up: Viessmann Boiler codes
Models
CA3B 2.5 BoilerCA3B 3.0 BoilerCA3B 3.5 BoilerCA3B 4.0 BoilerCA3B 5.0 BoilerCA3B 6.0 BoilerCA3B Series 2.5CA3B Series 3.0CA3B Series 3.5CA3B Series 4.0CA3B Series 5.0CA3B Series 6.0Vitocrossal 300 CA3B 2.5Vitocrossal 300 CA3B 3.5Vitocrossal 300 CA3B 4.0Vitocrossal 300 CA3B 5.0Vitocrossal 300 CA3B 6.0Vitocrossal 300 CA3B Series 2.5Vitocrossal 300 CA3B Series 3.0Vitocrossal 300 CA3B Series 3.5Vitocrossal 300 CA3B Series 4.0Vitocrossal 300 CA3B Series 5.0Vitocrossal 300 CA3B Series 6.0
More settings shortcuts tips for boiler
Source: Vitocrossal 300 CA3B service instructions, p. 24. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.