Warming things up…Dialing in your comfort…Almost cozy…
Reliable Heating and Cooling Solutions – Quality Service, Fair Prices, Guaranteed Satisfaction!

Viessmann Boiler: Service level overview

Updated · by Aurora Star Tech Inc.

Service level overview on a Viessmann boiler: Button combinations to reach the service functions.

Homeowner with a boiler problem? Call (647) 657-2977 or book a service call — licensed technicians across Vaughan and the GTA.

Applies to: Vitotronic 300 GW2

How to fix service level overview: step by step

  1. Temperatures, boiler coding cards and scans: menu and reset buttons together for about 2 seconds, exit with OK (p. 73).
  2. Relay test: menu and OK together for about 2 seconds, exit with OK (p. 68).
  3. LON participant check: w and OK together for about 2 seconds, exit by pressing w and OK for about 1 second (p. 66).
  4. Operating status information: press the status button (p. 77).
  5. Service scan (when Service is flashing): press OK (p. 74).
Safety: Gas, electrical and refrigerant work must be done by a licensed technician. Turn off power and gas before servicing, never bypass a safety control, and always follow the manufacturer's manual for your exact model.

If the unit shows an error code, look it up: Viessmann Boiler codes

More service & test modes tips for boiler

Source: Vitotronic 300 GW2 installation and service instructions, p. 72. Written in our own words as a summary; always check the original manual.

General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.