Viessmann Boiler: Run the actuator test
Run the actuator test on a Viessmann boiler: Forces outputs to check actuators. When the test starts, all actuators are disabled and valves move to their central position. Functions stay active for 30 seconds. If a function cannot run because of the current process, it is interrupted and a prompt appears. If max heating output is restricted by parameter 596.0, the boiler is skipped in the test.
Applies to: Vitocrossal 200 CI2 service menu
How to fix run the actuator test: step by step
- Enter the service menu and select Actuator test.
- Confirm the security prompt.
- Select the required group.
- Tap the required actuator function. Several can run at once.
- Confirm if prompted. Functions run for 30 seconds.
- End the actuator test with the exit option.
If the unit shows an error code, look it up: Viessmann Boiler codes
Models
399500750100015002000CI2 399CI2 399/500CI2 500CI2 750CI2 750/1000CI2 1000CI2 1500CI2 1500/2000CI2 2000Vitocrossal 200 CI2 399Vitocrossal 200 CI2 500Vitocrossal 200 CI2 750Vitocrossal 200 CI2 1000Vitocrossal 200 CI2 1500Vitocrossal 200 CI2 2000
More service & test modes tips for boiler
Source: Vitocrossal 200 CI2 Service Instructions, p. 55-56. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.