Viessmann Boiler: Route the pressure relief valve discharge
Route the pressure relief valve discharge on a Viessmann boiler: The relief valve discharge must be at least the outlet size, run horizontally over the side of the boiler, then drop vertically to about 1 ft (300 mm) above the floor, close to a floor drain.
Applies to: Pressure relief valve
How to fix route the pressure relief valve discharge: step by step
- Keep the discharge pipe the same size as the valve outlet.
- Run the pipe horizontally over the side of the boiler, then vertically down.
- End the pipe about 1 ft (300 mm) above the floor, as close to a floor drain as possible.
- Do not pipe the discharge outdoors or to an area where it can freeze.
- Secure the discharge pipe with hangers or brackets.
- Do not install any valve or obstruction between the boiler and the relief valve, or on its discharge side.
If the unit shows an error code, look it up: Viessmann Boiler codes
Models
399500750100015002000CI2 399CI2 399/500CI2 500CI2 750CI2 750/1000CI2 1000CI2 1500CI2 1500/2000CI2 2000Vitocrossal 200 CI2 399Vitocrossal 200 CI2 500Vitocrossal 200 CI2 750Vitocrossal 200 CI2 1000Vitocrossal 200 CI2 1500Vitocrossal 200 CI2 2000
Source: Vitocrossal 200 CI2 installation instructions, p. 40. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.