Viessmann Boiler: Room influence on supply temperature (worked example)
Room influence on supply temperature (worked example) on a Viessmann boiler: The supply temperature rise from room temperature hook-up is: (target room temp - actual room temp) x (1 + slope) x room influence factor / 4. Example from the manual: target 20.0°C, actual 18.0°C, slope 1.4, factor 8 (factory) gives a rise of 9.6 K.
Applies to: Heating circuits with room temperature hook-up
How to fix room influence on supply temperature (worked example): step by step
- Use the room influence factor parameter for the heating circuit: 933.7, 934.7, 935.7 or 936.7.
If the unit shows an error code, look it up: Viessmann Boiler codes
Models
399500750100015002000CI2 399CI2 399/500CI2 500CI2 750CI2 750/1000CI2 1000CI2 1500CI2 1500/2000CI2 2000Vitocrossal 200 CI2 399Vitocrossal 200 CI2 500Vitocrossal 200 CI2 750Vitocrossal 200 CI2 1000Vitocrossal 200 CI2 1500Vitocrossal 200 CI2 2000
Source: Viessmann Vitocrossal 200 CI2 service instructions, p. 86. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.