Viessmann Boiler: Replace motorized burner inlet damper
Replace motorized burner inlet damper on a Viessmann boiler: Removal of the motorized damper together with its servomotor and linkage. Equipped on CM2 246 and 311 only.
Applies to: CM2 246 and 311
How to fix replace motorized burner inlet damper: step by step
- Remove the four screws that hold the damper to the venturi tube and remove the damper with servomotor and linkage.
- Remove the servomotor cover.
- Unplug the servomotor.
- Disconnect the linkage from the servomotor shaft. Remove the bolts and the servomotor.
- Refit the servomotor, linkage and damper.
- Make sure the damper vents are fully open. Adjust the linkage if needed.
- Tighten to the torque in the torque table and reassemble in reverse order.
If the unit shows an error code, look it up: Viessmann Boiler codes
Models
186246311CM2 186 burnerCM2 246 burnerCM2 311 burnerVitocrossal 200 CM2 186Vitocrossal 200 CM2 246Vitocrossal 200 CM2 311Vitocrossal 200 CM2 400Vitocrossal 200 CM2 500Vitocrossal 200 CM2 620Vitocrossal 200 CM2 620 TX
Source: Vitocrossal 200 CM2 186 to 311 Service Instructions, p. 37. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.