Viessmann Boiler: Replace inlet damper linkage

Updated · by Aurora Star Tech Inc.

Replace inlet damper linkage on a Viessmann boiler: Linkage between the inlet damper bracket and the servomotor. Equipped on CM2 246 and 311 only.

Homeowner with a boiler problem? Call (647) 657-2977 or book a service call — licensed technicians across Vaughan and the GTA.

Applies to: CM2 246 and 311

How to fix replace inlet damper linkage: step by step

  1. Remove the M4 (8 mm hex) nut that connects the linkage to the inlet damper bracket.
  2. Loosen the M5 (4 mm hex key) set screw that connects the linkage to the servomotor.
  3. Remove the linkage and fit the new one.
  4. Make sure the damper vents are fully open. Adjust the linkage if needed.
  5. Tighten to the torque in the torque table and reassemble in reverse order.
Safety: Gas, electrical and refrigerant work must be done by a licensed technician. Turn off power and gas before servicing, never bypass a safety control, and always follow the manufacturer's manual for your exact model.

If the unit shows an error code, look it up: Viessmann Boiler codes

Models

186246311CM2 186 burnerCM2 246 burnerCM2 311 burnerVitocrossal 200 CM2 186Vitocrossal 200 CM2 246Vitocrossal 200 CM2 311Vitocrossal 200 CM2 400Vitocrossal 200 CM2 500Vitocrossal 200 CM2 620Vitocrossal 200 CM2 620 TX

Source: Vitocrossal 200 CM2 186 to 311 Service Instructions, p. 38. Written in our own words as a summary; always check the original manual.

General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.