Viessmann Boiler: Replace burner tube
Replace burner tube on a Viessmann boiler: Burner tube and retaining ring with gasket A.
Applies to: All CM2 models
How to fix replace burner tube: step by step
- Loosen the retaining clamp and disconnect the combustion air flex hose.
- Disconnect the gas line.
- Remove the four M12 (19 mm hex) burner door bolts and washers. Disconnect the gas line and plugs as in the burner door procedure.
- Remove the four M8 (13 mm hex) burner tube nuts from the burner door.
- Remove the burner tube with retaining ring and gasket A.
- Rotate the new tube until the studs line up with the holes in the burner door.
- Tighten the M8 nuts and M12 door bolts to the torque in the torque table.
- Leak test the reconnected gas line.
If the unit shows an error code, look it up: Viessmann Boiler codes
Models
186246311CM2 186 burnerCM2 246 burnerCM2 311 burnerVitocrossal 200 CM2 186Vitocrossal 200 CM2 246Vitocrossal 200 CM2 311Vitocrossal 200 CM2 400Vitocrossal 200 CM2 500Vitocrossal 200 CM2 620Vitocrossal 200 CM2 620 TX
Source: Vitocrossal 200 CM2 186 to 311 Service Instructions, p. 39. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.