Viessmann Boiler: Replace burner door
Replace burner door on a Viessmann boiler: Full burner door replacement, including fan, venturi and gas train removal.
Applies to: All CM2 models
How to fix replace burner door: step by step
- Loosen the retaining clamp and disconnect the combustion air flex hose. Disconnect the gas line.
- Unplug plugs 35, 36, 87, 111 and 122 from the burner control. Remove the burner control cover to reach plugs 87 and 111.
- Unplug fan plugs 100 and 100A. Disconnect pressure switch tubes APS1 from the venturi and APS2 from the burner door.
- Remove the four M8 nuts that connect the fan to the burner door. Remove the fan with venturi and gas train.
- Remove the two M6 bolts and the burner control assembly.
- Remove the ignition and ionization electrode block.
- Remove the cotter pins and hinge pins from the burner door.
- Remove the four M12 (19 mm hex) burner door bolts and washers.
- Remove the burner tube.
- Fit the new burner door. Install the door studs for the fan/venturi connection. Replace the barb fitting washer if needed.
- Tighten the fan/venturi nuts, the M12 door bolts and the M8 nuts to the torque in the torque table.
- Reassemble in reverse order and leak test the gas line.
If the unit shows an error code, look it up: Viessmann Boiler codes
Models
186246311CM2 186 burnerCM2 246 burnerCM2 311 burnerVitocrossal 200 CM2 186Vitocrossal 200 CM2 246Vitocrossal 200 CM2 311Vitocrossal 200 CM2 400Vitocrossal 200 CM2 500Vitocrossal 200 CM2 620Vitocrossal 200 CM2 620 TX
Source: Vitocrossal 200 CM2 186 to 311 Service Instructions, p. 40. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.