Updated · by Aurora Star Tech Inc.

Replace 2/2-way solenoid valve (choke valve) on a Viessmann boiler: Choke valve on the CM2 186 burner. The solenoid energises for about 5 seconds during ignition to add fan pressure to the gas regulator for a smoother light-off.

Homeowner with a boiler problem? Call (647) 657-2977 or book a service call — licensed technicians across Vaughan and the GTA.

Applies to: CM2 186 burner only

How to fix replace 2/2-way solenoid valve (choke valve): step by step

  1. Remove the connection hoses.
  2. Loosen the two screws and remove the valve. Note the installation direction.
  3. Loosen the plug screw and remove the plug.
  4. Loosen the hose fitting.
  5. Reassemble in reverse order.
Safety: Gas, electrical and refrigerant work must be done by a licensed technician. Turn off power and gas before servicing, never bypass a safety control, and always follow the manufacturer's manual for your exact model.

If the unit shows an error code, look it up: Viessmann Boiler codes

Models

186246311CM2 186 burnerCM2 246 burnerCM2 311 burnerVitocrossal 200 CM2 186Vitocrossal 200 CM2 246Vitocrossal 200 CM2 311Vitocrossal 200 CM2 400Vitocrossal 200 CM2 500Vitocrossal 200 CM2 620Vitocrossal 200 CM2 620 TX

Source: Vitocrossal 200 CM2 186 to 311 Service Instructions, p. 34. Written in our own words as a summary; always check the original manual.

General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.