Viessmann Boiler: Reduce operational input on burner control
Reduce operational input on burner control on a Viessmann boiler: Limit the maximum burner input between 0% (lower input) and 100% (upper input) if needed.
Applies to: Vitocrossal 200 CM2 burner control
How to fix reduce operational input on burner control: step by step
- Make sure the burner is in standby (Status 0, Service 0).
- Press button S and hold for more than 2 seconds until the display area flashes.
- Press button Y or E until 6 appears in the Service display.
- Press button S until 6 appears in the Status display.
- Press button S. A 1 appears in the Status display and the current max input (%) shows in the Service display.
- Press Y/E or B/G to set the required maximum input.
- Press S to confirm. A 1 shows on success; 0 means the adjustment failed.
- Press S to return to the operating display.
- Press button R for more than 2 seconds to restart and apply settings.
If the unit shows an error code, look it up: Viessmann Boiler codes
Models
186246311CM2 186 burnerCM2 246 burnerCM2 311 burnerVitocrossal 200 CM2 186Vitocrossal 200 CM2 246Vitocrossal 200 CM2 311Vitocrossal 200 CM2 400Vitocrossal 200 CM2 500Vitocrossal 200 CM2 620Vitocrossal 200 CM2 620 TX
More settings shortcuts tips for boiler
Source: Vitocrossal 200 CM2 186 to 311 Service Instructions, p. 14. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.