Viessmann Boiler: Read ionization current through the burner control
Read ionization current through the burner control on a Viessmann boiler: A multimeter cannot read ionization current. Use the burner control display sequence instead. The current should be at least 3 μA for 2 to 3 seconds after the gas valve opens and during operation.
Applies to: Vitocrossal 200 CM2 186 to 311
How to fix read ionization current through the burner control: step by step
- Press S F and hold for more than 2 seconds until the display area D flashes.
- Use Y E to set the service display to 5, then press S F so 5 shows in the status display.
- Use Y E to set the service display to .3, then press S F so 3 shows in the status display.
- Start the burner with the emissions test switch.
- Read the ionization current in the service display (for example 30 = 3.0 μA).
- Record the value on the maintenance record (page 64).
- Press S F and hold for more than 2 seconds, then use Y E to set the display to 5 and then 0.
- Press S F to return to the operating display.
If the unit shows an error code, look it up: Viessmann Boiler codes
Models
186246311CM2 186 burnerCM2 246 burnerCM2 311 burnerVitocrossal 200 CM2 186Vitocrossal 200 CM2 246Vitocrossal 200 CM2 311Vitocrossal 200 CM2 400Vitocrossal 200 CM2 500Vitocrossal 200 CM2 620Vitocrossal 200 CM2 620 TX
Source: Vitocrossal 200 CM2 186 to 311 Service Instructions, p. 17. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.