Viessmann Boiler: Read ionization current from the burner control
Read ionization current from the burner control on a Viessmann boiler: Ionization current must be read through the burner control, not with a meter.
Applies to: CA3B 2.5 to 6.0
How to fix read ionization current from the burner control: step by step
- Press the S button for about 2 seconds until the indicator blinks.
- Press the button until 5 shows under Service, then press S. 5 shows under Status.
- Press the button until 3 shows under Service, then press S. The ionization current appears under Service (for example 30 = 3.0 µA).
- Start the burner with the emissions test switch on the GW6C control.
- Read and record the ionization current.
- To exit, press S for about 2 seconds, set Service to 5 then S, set Service to 0 then S. The operating display returns.
If the unit shows an error code, look it up: Viessmann Boiler codes
Models
CA3B 2.5 BoilerCA3B 3.0 BoilerCA3B 3.5 BoilerCA3B 4.0 BoilerCA3B 5.0 BoilerCA3B 6.0 BoilerCA3B Series 2.5CA3B Series 3.0CA3B Series 3.5CA3B Series 4.0CA3B Series 5.0CA3B Series 6.0Vitocrossal 300 CA3B 2.5Vitocrossal 300 CA3B 3.5Vitocrossal 300 CA3B 4.0Vitocrossal 300 CA3B 5.0Vitocrossal 300 CA3B 6.0Vitocrossal 300 CA3B Series 2.5Vitocrossal 300 CA3B Series 3.0Vitocrossal 300 CA3B Series 3.5Vitocrossal 300 CA3B Series 4.0Vitocrossal 300 CA3B Series 5.0Vitocrossal 300 CA3B Series 6.0
More service & test modes tips for boiler
Source: Vitocrossal 300 CA3B Series 2.5 to 6.0 Service Instructions, p. 69. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.