Viessmann Boiler: Read ionization current
Read ionization current on a Viessmann boiler: Shows the ionization current in the process information menu. The value displays in 1/10 μA, so 30 means 3.0 μA.
Applies to: Vitocrossal 300 CA3B Series 2.5 to 6.0
How to fix read ionization current: step by step
- Press and hold button S for more than 2 seconds until it blinks.
- Press button Y until 5 shows under Service.
- Press button S. A 5 shows under Status.
- Press button Y until 3 shows under Service.
- Press button S. A 3 shows under Status and the ionization current shows under Service during operation.
- To exit, press and hold S for more than 2 seconds, then press Y until 5 shows under Service and press B until 0 shows.
- Press button S to return to the operating display.
If the unit shows an error code, look it up: Viessmann Boiler codes
Models
CA3B 2.5 BoilerCA3B 3.0 BoilerCA3B 3.5 BoilerCA3B 4.0 BoilerCA3B 5.0 BoilerCA3B 6.0 BoilerCA3B Series 2.5CA3B Series 3.0CA3B Series 3.5CA3B Series 4.0CA3B Series 5.0CA3B Series 6.0Vitocrossal 300 CA3B 2.5Vitocrossal 300 CA3B 3.5Vitocrossal 300 CA3B 4.0Vitocrossal 300 CA3B 5.0Vitocrossal 300 CA3B 6.0Vitocrossal 300 CA3B Series 2.5Vitocrossal 300 CA3B Series 3.0Vitocrossal 300 CA3B Series 3.5Vitocrossal 300 CA3B Series 4.0Vitocrossal 300 CA3B Series 5.0Vitocrossal 300 CA3B Series 6.0
More service & test modes tips for boiler
Source: Vitocrossal 300 CA3B Series 2.5 to 6.0 Service Instructions, p. 23. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.