Viessmann Boiler: Preventing oxygen-related corrosion in heating water
Preventing oxygen-related corrosion in heating water on a Viessmann boiler: Oxygen in the heating water causes corrosion of ferrous parts. Keep the system pressure above atmospheric at every point, including the pump suction side.
Applies to: Closed heating water systems
Common causes of preventing oxygen-related corrosion in heating water
- Open vented expansion vessels
- Negative pressure on the pump suction side
- Gas-permeable components such as some plastic underfloor pipes
How to fix preventing oxygen-related corrosion in heating water: step by step
- Check that the system pressure stays above atmospheric pressure at every point.
- Check the expansion vessel precharge pressure at least during the annual service.
- Separate permeable plastic pipe circuits from the boiler circuit with a corrosion-resistant heat exchanger.
- Where oxygen ingress is likely, add oxygen binder (sodium sulphite) at 5 to 10 ppm (5 to 10 mg/L).
- Keep the heating water pH between 8.2 and 9.5.
- Get a certificate of suitability for any chemical additive from its manufacturer.
If the unit shows an error code, look it up: Viessmann Boiler codes
Models
399500750100015002000CI2 399CI2 399/500CI2 500CI2 750CI2 750/1000CI2 1000CI2 1500CI2 1500/2000CI2 2000Vitocrossal 200 CI2 399Vitocrossal 200 CI2 500Vitocrossal 200 CI2 750Vitocrossal 200 CI2 1000Vitocrossal 200 CI2 1500Vitocrossal 200 CI2 2000
Source: Vitocrossal 200 CI2 service instructions, p. 95. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.