Viessmann Boiler: PP(s) and CPVC vent system limits

Updated · by Aurora Star Tech Inc.

PP(s) and CPVC vent system limits on a Viessmann boiler: PP(s) vent is flame-retardant polypropylene rated to a maximum of 230 F (110 C) and must be listed to ULC S636 or UL 1738. Do not mix pipe, fittings, or joining methods from different vent makers. CPVC vent must be Type BH Class IIB 90 C.

Homeowner with a boiler problem? Call (647) 657-2977 or book a service call — licensed technicians across Vaughan and the GTA.

Applies to: PP(s) and CPVC venting

How to fix pp(s) and cpvc vent system limits: step by step

  1. Confirm PP(s) components are listed to ULC S636 or UL 1738.
  2. Do not mix vent brands, fittings, or joining methods.
  3. For CPVC, use Type BH Class IIB 90 C pipe.
  4. For an existing vent reused with this boiler, seal it so room air cannot be drawn in as combustion air and confirm it is clean and in good condition.
  5. Count the vent and combustion air length in the equivalent length.
  6. If flexible vent or flexible air intake is used, reduce the maximum equivalent length by 25%.
Safety: Gas, electrical and refrigerant work must be done by a licensed technician. Turn off power and gas before servicing, never bypass a safety control, and always follow the manufacturer's manual for your exact model.

If the unit shows an error code, look it up: Viessmann Boiler codes

Models

399500750100015002000CI2 399CI2 399/500CI2 500CI2 750CI2 750/1000CI2 1000CI2 1500CI2 1500/2000CI2 2000Vitocrossal 200 CI2 399Vitocrossal 200 CI2 500Vitocrossal 200 CI2 750Vitocrossal 200 CI2 1000Vitocrossal 200 CI2 1500Vitocrossal 200 CI2 2000

Source: Vitocrossal 200 CI2 Installation Instructions, pp. 52-53. Written in our own words as a summary; always check the original manual.

General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.

Emergency Boiler Repair