Viessmann Boiler: Positioning and levelling the boiler
Positioning and levelling the boiler on a Viessmann boiler: The boiler must sit on a load-bearing foundation that allows for a neutralisation system connection. Levelling feet must be used once the boiler is in its final position. Dimension b is 29 in. (750 mm) for all models without seismic feet, and 46 in. (1170 mm) with seismic feet.
Applies to: Vitocrossal 200 CI2 399 to 2000
How to fix positioning and levelling the boiler: step by step
- Place the boiler on its final load-bearing foundation.
- Using an open-end wrench, adjust the levelling feet in the base frame until the wheels are off the ground.
- Place a flat steel plate under each levelling bolt for better weight distribution.
- Level the boiler by adjusting the levelling feet.
If the unit shows an error code, look it up: Viessmann Boiler codes
Models
399500750100015002000CI2 399CI2 399/500CI2 500CI2 750CI2 750/1000CI2 1000CI2 1500CI2 1500/2000CI2 2000Vitocrossal 200 CI2 399Vitocrossal 200 CI2 500Vitocrossal 200 CI2 750Vitocrossal 200 CI2 1000Vitocrossal 200 CI2 1500Vitocrossal 200 CI2 2000
Source: Vitocrossal 200 CI2 installation instructions, p. 11. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.