Viessmann Boiler: Low-loss header flow relationships
Low-loss header flow relationships on a Viessmann boiler: Relationships between boiler and system circuit flows when a low-loss header is used.
Applies to: Vitocrossal 300 CU3A with low-loss header
How to fix low-loss header flow relationships: step by step
- Confirm primary (boiler) flow is less than secondary (heating circuit) flow.
- Confirm secondary flow equals primary flow plus bypass flow.
- Confirm heat supplied by boiler equals heat consumed by system.
- Confirm boiler return temperature T2 equals system return temperature T4.
- Confirm boiler supply temperature T1 is higher than system supply temperature T3.
If the unit shows an error code, look it up: Viessmann Boiler codes
Models
CU3I 2ZC2ZP.01CU3I 3HC/Z3ZP.01CU3X 1ZC1ZP.01Vitocrossal 300 CU3A 26Vitocrossal 300 CU3A 35Vitocrossal 300 CU3A 45Vitocrossal 300 CU3A 57Vitocrossal 300 CU3A 94Vitocrossal 300 CU3A 125Vitocrossal 300 CU3A 160Vitocrossal 300 CU3A 199
More commissioning tips for boiler
Source: Vitocrossal 300 CU3A technical data manual, p. 17. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.