Commissioning: Boiler tips (part 13 of 21)

Updated · by Aurora Star Tech Inc.

Short, practical technician tips on commissioning for boiler. Check each one against the manual for your exact model before acting.

Low-loss header flow relationships

Viessmann · Vitocrossal 300 CU3A with low-loss header

Relationships between boiler and system circuit flows when a low-loss header is used.

  1. Confirm primary (boiler) flow is less than secondary (heating circuit) flow.
  2. Confirm secondary flow equals primary flow plus bypass flow.
  3. Confirm heat supplied by boiler equals heat consumed by system.
  4. Confirm boiler return temperature T2 equals system return temperature T4.
  5. Confirm boiler supply temperature T1 is higher than system supply temperature T3.

Low-loss header installation

Viessmann · Vitocrossal 300 CU3A with low-loss header

Use the low-loss header as a hydraulic break and for air and debris removal, especially when system head and flow rates are unknown.

  1. Install the header with the Viessmann temperature sensor at the TS connection, typically at the top of the header.
  2. Use only a Viessmann temperature sensor (accessory). Do not use another manufacturer's sensor.
  3. Check the maximum system flow rate for the header type against the table in this manual.
  4. Mount the header in the system as shown in the low-loss header design drawing.

Low-loss header is recommended when flow is high or unknown

Viessmann · Vitodens 200-W B2HB system piping

A low-loss header protects boiler flow when the system flow exceeds the boiler maximum, or when the system flow rate is not known.

  1. Check the system flow rate against the boiler maximum flow rate.
  2. If the flow may be higher, or is unknown, specify a low-loss header (accessory).

Low-loss header piping and air/debris removal

Viessmann · Low-loss header installations

In a low-loss header layout, system mixed supply temperature (T3) must be calculated per the manual formula. Temperatures T1 must be above 176°F (80°C) for the header design to work as shown. The header also removes air and debris from the heating system, so use the air bleed and drain valve connections.

  1. Connect boiler supply and return to the header boiler ports.
  2. Connect the system supply and return to the header system ports.
  3. Use the air bleed and drain valve to purge air and debris from the header.

Low-loss header sensor connection

Viessmann · Vitocrossal 300 CU3A with low-loss header

Where a low-loss header is used, connect the Viessmann temperature sensor at the TS connection, normally at the top of the header. This keeps boiler return temperatures low. Do not use another manufacturer's sensor.

  1. Install the Viessmann temperature sensor (accessory) at the TS connection on the low-loss header.
  2. Do not substitute a sensor from another manufacturer.

Marine and damp environments

Viessmann · Coastal or salt-air installations

Boiler casing and fan housing corrode quickly in salty, damp areas.

  1. Do not use direct vent (outdoor combustion air) in damp or salty marine locations.
  2. Use a room air dependent vent system in those locations.

Mechanical room ambient limits

Viessmann · All models

Boiler room must stay in the allowed temperature range and free of combustion air contaminants.

  1. Keep ambient temperature above 32°F (0°C) and below 104°F (40°C).
  2. Keep combustion air free of halogenated hydrocarbons and excessive dust.
  3. Avoid continuously high humidity.
  4. Never close existing ventilation openings.

Mechanical room and combustion air requirements

Viessmann · Vitodens 222-F B2TB

Mechanical room must stay between 32 °F (0 °C) and 104 °F (40 °C), be free of chemical and dust contamination, and keep humidity moderate. Never close existing ventilation openings.

  1. Check the room is heated, indoors, near a floor drain, and near an outside wall where possible.
  2. Keep halogenated hydrocarbons and excessive dust away from combustion air.
  3. In marine or salt-air areas, use a room-air-dependent vent system rather than direct vent.

Mechanical room location and air requirements

Viessmann · Vitorond 100 VR1 boilers

Install the boiler where fresh combustion air can reach it. The room must not be under negative pressure, and the boiler must not sit where chemicals, aggressive vapours or high dust or humidity are present.

  1. Install the boiler near an outside wall so fresh air can be ducted directly to the boiler area.
  2. Do not use exhaust, attic or dryer fans in the boiler room.
  3. Do not install the boiler in a room with refrigeration equipment or where chemicals are stored.
  4. Keep the boiler on a floor that can carry its filled weight, and do not block combustion air circulation.
  5. Place a concrete foundation under the boiler if the floor may flood, is not level, or the boiler is in a residential garage.
  6. In a garage, raise the burner at least 18 in. (457 mm) above the floor.
  7. Check local authority requirements for combustion air.

Mechanical room maximum temperature

Viessmann · Vitorond 200 VD2A

The mechanical room where the boiler is located must not exceed 104°F (40°C). Viessmann also recommends an extra electrical disconnect and a fuel shut-off valve outside the mechanical room, where possible.

  1. Check the mechanical room temperature stays at or below 104°F (40°C).
  2. Install an extra electrical disconnect and fuel shut-off outside the room if possible.

Mixing valve circuits need the actuator kit and supply sensor

Viessmann · Vitotronic 300 KW3 with one or more mixing valve circuits

Each heating circuit with a mixing valve needs a mixing valve actuator accessory kit. The kit includes the mixing valve motor and the supply temperature sensor, which connect to the control.

  1. Order one actuator kit per mixing valve circuit.
  2. Use the 7133 392 kit on older valves or the 7837 524 kit on newer valves.
  3. Connect the supply temperature sensor from the kit to the control.

Mixing valve control options

Viessmann · Vitodens 200-W B2HA 45, 60 mixing valve circuits

The built-in 3-way mixing valve for low-temperature circuits is controlled by an accessory kit for a heating circuit with mixing valve. Alternatively, a Vitotronic 200-H HK1B mixing valve control with LON communication module can be used instead of the kit and Vitocontrol.

  1. Fit the accessory kit for a heating circuit with mixing valve to control the 3-way mixing valve.
  2. Or use Vitotronic 200-H HK1B with the LON communication module instead of the kit and Vitocontrol.
  3. For complex multi-circuit designs, contact the local Viessmann sales representative.

Mixing valve type selection

Viessmann · Mixing valve circuits

Condensing boilers have low return water temperatures, so only 3-way mixing valves are allowed on them. Non-condensing boilers can use a 4-way valve.

  1. On condensing boilers, install only 3-way mixing valves.
  2. On non-condensing boilers such as Vitogas 100, Vitorond 200 and Vitola 200, a 4-way mixing valve may be used.
  3. Order the circulation pump with flow check valve for DHW tank control separately.

Mixing valves and underfloor heating

Viessmann · Vitocrossal 300 CU3A heating circuit design

Rules for mixing valves and underfloor tubing.

  1. Avoid mixing valves in heating circuits where possible, because condensing needs low return temperatures.
  2. If a mixing valve is required, use only 3-way mixing valves. Do not use 4-way mixing valves.
  3. Connect underfloor systems with large water volumes through a 3-way mixing valve.
  4. Separate underfloor systems that use tubing without an oxygen diffusion barrier from the boiler with a heat exchanger.

Mixing valves on condensing systems

Viessmann · Hydronic system layout

Condensing operation needs low return temperatures, so avoid mixing valves in the heating circuit where possible.

  1. Avoid mixing valves in the heating circuit where possible.
  2. If a mixing valve is needed (multi-circuit or underfloor), use only 3-way mixing valves.
  3. Do not use 4-way mixing valves with condensing boilers.

Modbus RS-485 wiring

Viessmann · Versatronik 502 and 502D MODBUS gateway

Use COM 1 terminals A and B for Modbus. A is the non-inverting (+) line and B is the inverting (-) line. Naming can differ between manufacturers, so check the DDC system. The gateway has no termination resistor, so handle termination at the network. Two 4.7 kOhm pull-up/pull-down bias resistors are on the lines.

  1. Connect the DDC network to COM 1 terminals A and B on the gateway.
  2. Confirm A is (+) and B is (-) against the DDC system labelling.
  3. Add termination at the network end, because the gateway does not provide it.
  4. Confirm the Modbus device address is set on the rotary dial.

Modbus RS-485 wiring and termination

Viessmann · Versatronik 502 and 502D gateway, all listed controls

Use COM 1 terminals A and B. Terminal naming differs between manufacturers, so A is the non-inverting (+) line and B is the inverting (-) line. The gateway has no termination resistor, only two weak 4.7 kOhm pull up/down bias resistors on the lines. Add termination at the network ends as the Modbus network requires.

  1. Connect the field Modbus wiring to COM 1 terminals A and B.
  2. Match A to the (+) non-inverting side and B to the (-) inverting side of the DDC network.
  3. Do not rely on the gateway for line termination; provide it on the network if needed.

Mounting the 120VAC gateway

Viessmann · Versatronik 585 (120VAC)

Mount the 120VAC gateway near the boiler control. Loosen the two screws on the base to remove the cover, fix the base to the wall, and remove a knockout for the strain relief or box connector. Reinstall the cover after all 120VAC and low-voltage wiring is done and checked.

  1. Remove the cover by loosening the two screws on each side of the base.
  2. Fasten the base to the wall with field-supplied fasteners.
  3. Remove one knockout and fit the strain relief or box connector.
  4. Remove the other knockouts only as needed for connections.
  5. Complete and verify all 120VAC and low-voltage wiring, then refit the cover.

Mounting the 24VAC DIN rail gateway

Viessmann · Versatronik 585D (24VAC)

The 585D mounts on a DIN rail inside an enclosure near the boiler controls. It needs a field-supplied 24VAC power connection.

  1. Mount the 585D gateway on a DIN rail inside an enclosure close to the boiler controls.
  2. Make all connections, including the field-supplied 24VAC power supply.
  3. Check the connection overview: BACnet IP RJ45, control BACnet RJ45, paralleled BUS connection, and 24VAC power.

Multi boiler fault message at first start-up

Viessmann · Vitocrossal 200 CM2 in multi boiler systems

A fault message appears on first start-up of a CM2 boiler in a multiple boiler application because the boiler controller commissioning is not finished.

  1. Acknowledge the fault message.
  2. Complete the commissioning process.

Multi-boiler and zone control capability

Viessmann · Vitocrossal 300 CU3A 26 to 199

Up to 8 boilers can be installed in multi-boiler configuration up to 1592 MBH (464 kW). The Vitotronic control provides 3 zone circuit inputs for third party thermostats, SIM controls, multizone controllers, and on/off devices. Setup uses a start-up wizard.

  1. Use the start-up wizard to enter the relevant system information.
  2. Set each zone circuit to a set temperature or an outdoor reset curve as needed.

Multi-boiler systems without Vitotronic 333

Viessmann · Circuit Diagrams 5, 6, 7 and 8 multi-boiler systems

Cascade and DHW tank control must be activated by a building automation system.

  1. Confirm building automation activates cascade staging and DHW tank control before commissioning.

Never adjust the burner by eye

Viessmann · Oil burner adjustment

Burner settings must be measured, not judged visually.

  1. Set the burner using combustion measurements from calibrated equipment only.

Never check gas leaks with an open flame

Viessmann · Vitodens 200-W B2HA gas connections

Use only approved leak detection solution for gas leak checks.

  1. Check gas connections with an approved liquid spray solution, not an open flame.

No flow switch required

Viessmann · Vitocrossal 300 CU3A 26 to 199

This boiler does not use a flow switch. It is only suitable for fully pumped hot water heating systems.

No isolation valve between boiler and safety header

Viessmann · Safety piping

Do not install an isolation valve between the boiler and the safety header or between the relief valve and the boiler. The relief discharge must be routed so it cannot scald people.

  1. Pipe the relief discharge so it cannot scald attendants.
  2. Keep the relief discharge pipe as short and straight as possible, with an elbow close to the valve outlet.

Non-Viessmann DHW tank

Viessmann · Non-Viessmann DHW storage tanks

If the DHW storage tank is not a Viessmann Vitocell 100 or 300, the DHW tank temperature sensor must be checked with the tank manufacturer. A temperature tempering valve is strongly recommended in the DHW supply line.

  1. Verify the DHW tank temperature sensor operation with the tank's original manufacturer.
  2. Install a temperature tempering valve in the DHW supply line.

Non-Viessmann DHW tank checks

Viessmann · Non-Viessmann DHW storage tanks

With a DHW tank that is not a Viessmann Vitocell 100 or 300, the installer must confirm the Viessmann DHW tank sensor works correctly with the tank maker. The coil pressure drop must also be calculated against the field pump's residual head to make sure enough flow reaches the boiler heat exchanger.

  1. Verify the Viessmann DHW tank temperature sensor operation with the original tank manufacturer.
  2. Calculate DHW coil pressure drop and compare it with the field pump's residual head.
  3. Confirm the boiler heat exchanger still gets sufficient flow.

Non-Viessmann DHW tank sensor check

Viessmann · Non-Viessmann DHW storage tanks

With a DHW tank other than a Viessmann Vitocell 100 or 300, the Viessmann DHW tank sensor must be checked against the tank maker's data. A temperature tempering valve is strongly recommended in the DHW supply line.

  1. Confirm with the tank manufacturer that the Viessmann DHW tank sensor operates correctly on that tank.
  2. Install a temperature tempering valve in the DHW supply line.

Only a licensed heating contractor may install and service

Viessmann · Vitorond 200 VD2 boilers

Installation, adjustment, service and maintenance must be done by a licensed professional heating contractor experienced with hot water boilers. There are no user-serviceable parts on the boiler, burner or control.

Safety: Gas, electrical and refrigerant work must be done by a licensed technician. Turn off power and gas before servicing, never bypass a safety control, and always follow the manufacturer's manual for your exact model.

General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.