Viessmann Boiler: Louver sizing for combustion air openings
Louver sizing for combustion air openings on a Viessmann boiler: If the free area of louvers is unknown, assume 20% free area for wood and 60-75% for metal louvers. Openings must be made larger to allow for louver restriction. Example: a free 14 in x 6 in (356 x 152 mm) opening becomes 14 in x 10 in (356 x 254 mm) with metal louvers.
Applies to: Closet combustion air openings
How to fix louver sizing for combustion air openings: step by step
- Find the free area of the louver from the maker.
- If unknown, assume 20% for wood louvers.
- If unknown, assume 60-75% for metal louvers.
- Enlarge the opening so the free area is met after the louver.
If the unit shows an error code, look it up: Viessmann Boiler codes
Models
399500750100015002000CI2 399CI2 399/500CI2 500CI2 750CI2 750/1000CI2 1000CI2 1500CI2 1500/2000CI2 2000Vitocrossal 200 CI2 399Vitocrossal 200 CI2 500Vitocrossal 200 CI2 750Vitocrossal 200 CI2 1000Vitocrossal 200 CI2 1500Vitocrossal 200 CI2 2000
Source: Vitocrossal 200 CI2 Installation Instructions, p. 55. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.