Viessmann Boiler: Install auxiliary low gas pressure switch
Install auxiliary low gas pressure switch on a Viessmann boiler: Fit and wire the auxiliary low gas pressure switch on the gas line, then set it and leak test.
Applies to: Auxiliary low gas pressure switch
How to fix install auxiliary low gas pressure switch: step by step
- Disconnect boiler power.
- If the boiler is already installed, shut off the main gas supply and disconnect the gas piping.
- Install the gas piping components as required.
- Route the cable under the top rail and secure it with plug-in cable retainers.
- Wire the switch: green to ground G, white to 26 (L) COM, black to 27 (L) NO.
- Set the low gas pressure switch to 4.5 in. w.c.
- Open the gas supply to the burner.
- Leak test the gas line and the switch with an approved gas leak detector.
- Reconnect boiler power.
If the unit shows an error code, look it up: Viessmann Boiler codes
Models
186246311CM2 186 burnerCM2 246 burnerCM2 311 burnerVitocrossal 200 CM2 186Vitocrossal 200 CM2 246Vitocrossal 200 CM2 311Vitocrossal 200 CM2 400Vitocrossal 200 CM2 500Vitocrossal 200 CM2 620Vitocrossal 200 CM2 620 TX
Source: Vitocrossal 200 CM2 186 to 311 service instructions, p. 27. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.