Viessmann Boiler: Hydrostatic test pressure limits
Hydrostatic test pressure limits on a Viessmann boiler: Minimum test pressure is 127 psig (875 kPa). Maximum is 130 psig (896 kPa), which is also 1½ times the maximum operating pressure. Do not exceed 130 psig.
Applies to: All VD2A models
How to fix hydrostatic test pressure limits: step by step
- Set the test between 127 and 130 psig and hold for 30 minutes.
If the unit shows an error code, look it up: Viessmann Boiler codes
More commissioning tips for boiler
Source: Vitorond 200, VD2A Series Installation, pp. 21, 24. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.