Viessmann Boiler: Heating system layout and mixing valves
Heating system layout and mixing valves on a Viessmann boiler: Recommended maximum boiler supply temperature is 158°F (70°C) for heating and DHW to limit distribution losses. Avoid mixing valves on the heating circuit where possible because condensing boilers need low return temperatures. If a mixing valve is needed (multi-zone or underfloor), use only 3-way mixing valves. Never use 4-way mixing valves with condensing boilers. Underfloor systems and large-volume loops must connect through a 3-way mixing valve.
Applies to: Vitodens 222-F, B2TB 68 and 125
How to fix heating system layout and mixing valves: step by step
- Set max boiler supply temperature to 158°F (70°C) where possible.
- Avoid mixing valves on the heating circuit when possible.
- Use 3-way mixing valves only.
- Do not use 4-way mixing valves.
If the unit shows an error code, look it up: Viessmann Boiler codes
Models
222-F B2TB 19222-F B2TB 35222-F B2TB 68222-F B2TB 125B2TB 19B2TB 35B2TB 68B2TB 125VD2T 1HC1T4ZP.01VD2T 1HC1T4ZV.01Vitodens 222-F, B2TB 19Vitodens 222-F, B2TB 35Vitodens 222-F, B2TB 68Vitodens 222-F, B2TB 125
More commissioning tips for boiler
Source: Vitodens 222-F B2TB application guide, p. 17. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.