Viessmann Boiler: Heating circuit controls not on LON bus

Updated · by Aurora Star Tech Inc.

Heating circuit controls not on LON bus on a Viessmann boiler: When downstream heating circuit controls are not connected to the boiler control unit via LON, the temperature sensor and plug wiring must match the coding.

Homeowner with a boiler problem? Call (647) 657-2977 or book a service call — licensed technicians across Vaughan and the GTA.

Applies to: Circuit diagrams 3, 4 and 5

How to fix heating circuit controls not on lon bus: step by step

  1. Wire temperature sensor T1 or T2 to plug aJA or aJB as shown in the circuit diagram.
  2. Set the matching coding (4A: 1 or 4b: 1 is set automatically when the sensor is connected).
  3. If sensor T1 closes the downstream mixing valves, set 4C: 2 and use plug sÖ (A1).
Safety: Gas, electrical and refrigerant work must be done by a licensed technician. Turn off power and gas before servicing, never bypass a safety control, and always follow the manufacturer's manual for your exact model.

If the unit shows an error code, look it up: Viessmann Boiler codes

Models

Vitotronic 100, type GC1

More commissioning tips for boiler

Source: Vitotronic 100 GC1 installation and service instructions, p. 9. Written in our own words as a summary; always check the original manual.

General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.