Viessmann Boiler: DIP switch for separate room temperature sensor

Updated · by Aurora Star Tech Inc.

DIP switch for separate room temperature sensor on a Viessmann boiler: When a separate room temperature sensor is connected to a remote control, set the matching DIP switch to ON on the remote control's printed circuit board (rear of top casing).

Homeowner with a boiler problem? Call (647) 657-2977 or book a service call — licensed technicians across Vaughan and the GTA.

Applies to: Vitotrol 200 and Vitotrol 300 with separate room temperature sensor

How to fix dip switch for separate room temperature sensor: step by step

  1. Vitotrol 200: set DIP switch S6.3 to ON.
  2. Vitotrol 300: set DIP switch S30.3 to ON.
  3. For Vitotrol 300 also set coding switch 3 to ON when using the separate room temperature sensor (see the room temperature sensor section).
Safety: Gas, electrical and refrigerant work must be done by a licensed technician. Turn off power and gas before servicing, never bypass a safety control, and always follow the manufacturer's manual for your exact model.

If the unit shows an error code, look it up: Viessmann Boiler codes

More settings shortcuts tips for boiler

Source: Vitotronic 300, Model GW2 installation and service instructions, p. 107, 109. Written in our own words as a summary; always check the original manual.

General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.