Viessmann Boiler: Conversion to natural gas (NG)
Conversion to natural gas (NG) on a Viessmann boiler: Convert the burner from LPG back to natural gas. No separate orifice is needed for natural gas.
Applies to: Vitocrossal 200 CM2 186 to 311 boilers
How to fix conversion to natural gas (ng): step by step
- Close the gas shut-off valve.
- Switch off the system ON/OFF switch at the boiler control unit.
- Switch off the main boiler circuit breaker or power supply and prevent reconnection.
- Remove the boiler front cover.
- Undo gas supply fitting A and disconnect compensation tubing B.
- Remove four 8 mm hex nuts and detach the gas valve from flange C.
- Remove and dispose of the LPG orifice D and the rubberized cork gaskets E.
- Install a new rubberized cork gasket between the gas valve and flange C.
- Secure the gas valve to flange C. Torque nuts diagonally to 17.7 lb-in (2.0 Nm).
- Secure and tighten gas supply fitting A and reconnect compensation tubing B.
- Apply the partial rating plate, the labels and complete the conversion report.
- Check all gas fittings for leaks.
If the unit shows an error code, look it up: Viessmann Boiler codes
Models
186246311CM2 186 burnerCM2 246 burnerCM2 311 burnerVitocrossal 200 CM2 186Vitocrossal 200 CM2 246Vitocrossal 200 CM2 311Vitocrossal 200 CM2 400Vitocrossal 200 CM2 500Vitocrossal 200 CM2 620Vitocrossal 200 CM2 620 TX
Source: Vitocrossal 200 CM2 186 to 311 Service Instructions, p. 12. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.