Viessmann Boiler: Combustion air interlock (CAI) for motorized ventilation air supply
Combustion air interlock (CAI) for motorized ventilation air supply on a Viessmann boiler: A motorized ventilation air supply with or without feedback connects to the CAI plug. The burner does not start until feedback is present.
Applies to: CAI plug
How to fix combustion air interlock (cai) for motorized ventilation air supply: step by step
- Connect the fan or damper to the CAI plug.
- If the device has no feedback, keep the jumper across R and W in place.
- If the device has feedback, remove the jumper.
- Set parameters per the Service Instructions.
If the unit shows an error code, look it up: Viessmann Boiler codes
Models
399500750100015002000CI2 399CI2 399/500CI2 500CI2 750CI2 750/1000CI2 1000CI2 1500CI2 1500/2000CI2 2000Vitocrossal 200 CI2 399Vitocrossal 200 CI2 500Vitocrossal 200 CI2 750Vitocrossal 200 CI2 1000Vitocrossal 200 CI2 1500Vitocrossal 200 CI2 2000
Source: Vitocrossal 200 CI2 Installation Instructions, p. 25. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.