Clean combustion chamber and heating surfaces on a Viessmann boiler: Cleaning of the combustion chamber and heat exchanger surfaces. For CI2 1500 and 2000, clean both combustion chambers.

Homeowner with a boiler problem? Call (647) 657-2977 or book a service call — licensed technicians across Vaughan and the GTA.

Applies to: Vitocrossal 200 CI2

How to fix clean combustion chamber and heating surfaces: step by step

  1. Remove 3 cotter pins.
  2. Open and remove the inspection cover.
  3. Flush the combustion chamber and heating surfaces with water using a 90° angled pressure-washer nozzle.
  4. Apply cleaning agent and let it soak per the manufacturer's instructions.
  5. Use stainless-steel-safe cleaner; alkaline with surfactant for soot; slightly acidic chloride-free phosphoric-acid type for coatings and yellow-brown discoloration.
  6. Keep cleaning agent out between the boiler body and thermal insulation.
  7. Flush again until no cleaning agent residue remains; repeat if needed.
  8. Reassemble: check the gasket, lubricate it with suitable paste, refit the cover and insert the cotter pins.
  9. Carry out a seal test (mirror or electrical sensor) after reassembly.
Safety: Gas, electrical and refrigerant work must be done by a licensed technician. Turn off power and gas before servicing, never bypass a safety control, and always follow the manufacturer's manual for your exact model.

If the unit shows an error code, look it up: Viessmann Boiler codes

Models

399500750100015002000CI2 399CI2 399/500CI2 500CI2 750CI2 750/1000CI2 1000CI2 1500CI2 1500/2000CI2 2000Vitocrossal 200 CI2 399Vitocrossal 200 CI2 500Vitocrossal 200 CI2 750Vitocrossal 200 CI2 1000Vitocrossal 200 CI2 1500Vitocrossal 200 CI2 2000

Source: Vitocrossal 200 CI2 service instructions, p. 31. Written in our own words as a summary; always check the original manual.

General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.