Viessmann Boiler: Check tank, supply or low loss header temperature sensor

Updated · by Aurora Star Tech Inc.

Check tank, supply or low loss header temperature sensor on a Viessmann boiler: Resistance check of the NTC 10 kOhm tank, supply or low loss header sensor.

Homeowner with a boiler problem? Call (647) 657-2977 or book a service call — licensed technicians across Vaughan and the GTA.

Applies to: Vitocrossal 200 CI2

Common causes of check tank, supply or low loss header temperature sensor

  • Faulty sensor (resistance deviates more than 10%)

How to fix check tank, supply or low loss header temperature sensor: step by step

  1. Disconnect plug TS1 or the sensor from the electronics module.
  2. Measure the sensor resistance.
  3. Compare it with the NTC curve.
  4. If the deviation is more than 10%, replace the sensor.
Safety: Gas, electrical and refrigerant work must be done by a licensed technician. Turn off power and gas before servicing, never bypass a safety control, and always follow the manufacturer's manual for your exact model.

If the unit shows an error code, look it up: Viessmann Boiler codes

Models

399500750100015002000CI2 399CI2 399/500CI2 500CI2 750CI2 750/1000CI2 1000CI2 1500CI2 1500/2000CI2 2000Vitocrossal 200 CI2 399Vitocrossal 200 CI2 500Vitocrossal 200 CI2 750Vitocrossal 200 CI2 1000Vitocrossal 200 CI2 1500Vitocrossal 200 CI2 2000

Source: Vitocrossal 200 CI2 Service Instructions, p. 78. Written in our own words as a summary; always check the original manual.

General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.