Viessmann Boiler: Check gas side connections for leaks
Check gas side connections for leaks on a Viessmann boiler: Use new gaskets on all gas fittings separated on site. Do not use leak detection spray near electrical contacts, as it can cause faulty operation.
Applies to: Vitocrossal 200 CI2 boilers
Common causes of check gas side connections for leaks
- Gas fitting gasket leak
How to fix check gas side connections for leaks: step by step
- Insert new gaskets in all gas fittings separated on site.
- Open the gas shut-off valve.
- Check the sealing points of the gas solenoid valve for leaks.
- Start the burner (see page 25).
- Check the outlet sealing points of the gas solenoid valve.
- Check the sealing point between the fan and the burner plate.
- Check the sealing point between the fan and the Venturi pipe.
If the unit shows an error code, look it up: Viessmann Boiler codes
Models
399500750100015002000CI2 399CI2 399/500CI2 500CI2 750CI2 750/1000CI2 1000CI2 1500CI2 1500/2000CI2 2000Vitocrossal 200 CI2 399Vitocrossal 200 CI2 500Vitocrossal 200 CI2 750Vitocrossal 200 CI2 1000Vitocrossal 200 CI2 1500Vitocrossal 200 CI2 2000
Source: Vitocrossal 200 CI2 Service Instructions, p. 34. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.