Viessmann Boiler: Check expansion vessel pre-charge and system pressure
Check expansion vessel pre-charge and system pressure on a Viessmann boiler: Carry out this check on a cold system and follow the expansion vessel manufacturer's instructions. Permissible operating pressure is 80 psi (5.5 bar).
Applies to: Vitocrossal 200 CI2 boilers
Common causes of check expansion vessel pre-charge and system pressure
- Pre-charge lower than static system pressure
How to fix check expansion vessel pre-charge and system pressure: step by step
- Drain the system until the manometer reads 0, or close the cap valve on the expansion vessel and reduce the vessel pressure.
- If the pre-charge is lower than the static system pressure, top up with nitrogen until the pre-charge is 1 to 2 psi (0.1 to 0.2 bar) higher.
- Top up with water until the cooled system charge pressure is 1 to 2 psi (0.1 to 0.2 bar) higher than the vessel pre-charge.
- Confirm the system stays below 80 psi (5.5 bar).
If the unit shows an error code, look it up: Viessmann Boiler codes
Models
399500750100015002000CI2 399CI2 399/500CI2 500CI2 750CI2 750/1000CI2 1000CI2 1500CI2 1500/2000CI2 2000Vitocrossal 200 CI2 399Vitocrossal 200 CI2 500Vitocrossal 200 CI2 750Vitocrossal 200 CI2 1000Vitocrossal 200 CI2 1500Vitocrossal 200 CI2 2000
Source: Vitocrossal 200 CI2 Service Instructions, p. 35. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.