Viessmann Boiler: Check condensate drain and neutralizing unit
Check condensate drain and neutralizing unit on a Viessmann boiler: If condensate does not drain, it builds up in the boiler and the burner shuts down with a fault message.
Applies to: Vitocrossal 200 CM2 186 to 311
Common causes of check condensate drain and neutralizing unit
- Blocked or contaminated condensate drain
- Exhausted neutralizing granulate
How to fix check condensate drain and neutralizing unit: step by step
- Check condensate pH with a pH strip. Replace granulate if pH is below 6.5.
- If contaminated, rinse the neutralizing unit with tap water.
- Add granulate up to the minimum level marked in red.
- Pull off the drain hose and clean the drain hose and pipe at least once a year.
- Flush lower part D of siphon B, refill with water and reassemble.
- Reconnect the neutralizing hose to the siphon.
- Add water to the combustion chamber and confirm it drains without back pressure. Clean the drain again if needed.
If the unit shows an error code, look it up: Viessmann Boiler codes
Models
186246311CM2 186 burnerCM2 246 burnerCM2 311 burnerVitocrossal 200 CM2 186Vitocrossal 200 CM2 246Vitocrossal 200 CM2 311Vitocrossal 200 CM2 400Vitocrossal 200 CM2 500Vitocrossal 200 CM2 620Vitocrossal 200 CM2 620 TX
Source: Vitocrossal 200 CM2 186 to 311 Service Instructions, p. 19. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.