Viessmann Boiler: Changeover contact 66 for fault output or external boiler demand

Updated · by Aurora Star Tech Inc.

Changeover contact 66 for fault output or external boiler demand on a Viessmann boiler: Contact 66 can report a fault or request heat from an external boiler. With supplemental enabled, it closes when full-load operation fails to reach setpoint for a set time.

Homeowner with a boiler problem? Call (647) 657-2977 or book a service call — licensed technicians across Vaughan and the GTA.

Applies to: Potential-free changeover contact 66

How to fix changeover contact 66 for fault output or external boiler demand: step by step

  1. Set the function in parameter 1706.0 (Boiler group).
  2. Wire the fault or demand signal to contact 66 (NC, NO or COM as needed).
  3. Check the rated current of 2 A is not exceeded.
Safety: Gas, electrical and refrigerant work must be done by a licensed technician. Turn off power and gas before servicing, never bypass a safety control, and always follow the manufacturer's manual for your exact model.

If the unit shows an error code, look it up: Viessmann Boiler codes

Models

399500750100015002000CI2 399CI2 399/500CI2 500CI2 750CI2 750/1000CI2 1000CI2 1500CI2 1500/2000CI2 2000Vitocrossal 200 CI2 399Vitocrossal 200 CI2 500Vitocrossal 200 CI2 750Vitocrossal 200 CI2 1000Vitocrossal 200 CI2 1500Vitocrossal 200 CI2 2000

Source: Vitocrossal 200 CI2 Installation Instructions, p. 25. Written in our own words as a summary; always check the original manual.

General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.