Viessmann Boiler: Boiler control and harness mounting
Boiler control and harness mounting on a Viessmann boiler: The control housing and burner harness bracket mount to the side panel. Capillaries and the boiler sensor must stay away from heat sources such as the vent, chimney and supply or return piping.
Applies to: Vitorond 200 VD2A boiler
How to fix boiler control and harness mounting: step by step
- Drill the four mounting holes on the side panel as shown (mirror the drawing for left-side mount) and punch the 7/8 in. (22 mm) opening.
- Install the control harness bracket with the supplied 8-32 self-tapping screws.
- Install the burner harness bracket with two supplied screws.
- Remove the two plugs on the back of the control housing and mount it on the side panel with two screws.
- Run capillaries and the boiler temperature sensor through the side opening and insert the sensor into the sensor well as far as possible.
- Install the top panels and the name plate.
- In Canada, install the oil door safety switch per its separate instructions.
- Follow the boiler control installation instructions for electrical connections.
If the unit shows an error code, look it up: Viessmann Boiler codes
Source: Vitorond 200, VD2A Series Installation, p. 27-28. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.