Viessmann Boiler: Assembling PP(s) and stainless vent pipe
Assembling PP(s) and stainless vent pipe on a Viessmann boiler: Keep the vent route short and direct with as few bends as possible. Pipe must slope back to the boiler so condensate drains from the flue to the boiler. Use only the vent maker's parts with PP(s) systems.
Applies to: Vitocrossal 300 CA3B Dual Fuel venting
How to fix assembling pp(s) and stainless vent pipe: step by step
- Check that the gaskets are seated in the rigid pipe collars.
- Lubricate the pipe ends and collars with water, then slide the pieces together with a gentle twist.
- Slope the vent at least 2 to 3 degrees toward the boiler. For a 3 degree slope, use about 2 in. per 3.3 ft (50 mm per 1 m).
- Cut pipe square with a hacksaw or snips, file the edges smooth, and keep the pipe round.
- Deburr and clean the pipe after cutting.
- Follow the vent manufacturer's installation instructions alongside this manual.
- Keep elbows to a minimum, avoid back-to-back 90 degree elbows, and use 45 degree elbows where possible.
- Do not route the vent through or inside another vent or chimney, except a masonry flue used only by this boiler.
If the unit shows an error code, look it up: Viessmann Boiler codes
Models
2.53.04.05.06.0CA3B 2.5CA3B 3.0CA3B 3.5CA3B 4.0CA3B 5.0CA3B 6.0CA3B Dual Fuel 2.5CA3B Dual Fuel 2.5 BoilerCA3B Dual Fuel 3.0CA3B Dual Fuel 3.0 BoilerCA3B Dual Fuel 3.5CA3B Dual Fuel 3.5 BoilerCA3B Dual Fuel 4.0CA3B Dual Fuel 4.0 BoilerCA3B Dual Fuel 5.0CA3B Dual Fuel 5.0 BoilerCA3B Dual Fuel 6.0CA3B Dual Fuel 6.0 BoilerCA3B Dual Fuel Series 2.5CA3B Dual Fuel Series 3.0CA3B Dual Fuel Series 3.5CA3B Dual Fuel Series 4.0CA3B Dual Fuel Series 5.0CA3B Dual Fuel Series 6.0Vitocrossal 300 CA3B Dual Fuel 2.5Vitocrossal 300 CA3B Dual Fuel 3.0Vitocrossal 300 CA3B Dual Fuel 3.5Vitocrossal 300 CA3B Dual Fuel 4.0Vitocrossal 300 CA3B Dual Fuel 5.0Vitocrossal 300 CA3B Dual Fuel 6.0Vitocrossal 300 CA3B Dual Fuel Series 2.5Vitocrossal 300 CA3B Dual Fuel Series 3.0Vitocrossal 300 CA3B Dual Fuel Series 3.5Vitocrossal 300 CA3B Dual Fuel Series 4.0Vitocrossal 300 CA3B Dual Fuel Series 5.0Vitocrossal 300 CA3B Dual Fuel Series 6.0
More commissioning tips for boiler
Source: Vitocrossal 300 CA3B Dual Fuel installation manual, p. 49. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.