Viessmann Boiler: Application 8 design notes
Application 8 design notes on a Viessmann boiler: Design notes for the Application 8 layout.
Applies to: Application 8 (2CU3I 3HC/ZC3ZP.01)
How to fix application 8 design notes: step by step
- Note that the air handler circulator is not controlled by the boiler, so higher than design water temperatures can reach the air handler during DHW calls.
- CU3A is a high mass boiler, so primary/secondary piping is not required.
- The low loss header can be replaced with closely spaced tees (see Application 9).
- Cascade control max load is 6 amps. Use isolation relays if multiple circulators and mixing valve motors are used.
- P5 is controlled internally by the air handler.
- Verify mixing valve motor stroke direction with an actuator test (see Cascade Control Installation & Service Manual).
If the unit shows an error code, look it up: Viessmann Boiler codes
Models
CU3I 2ZC2ZP.01CU3I 3HC/Z3ZP.01CU3X 1ZC1ZP.01Vitocrossal 300 CU3A 26Vitocrossal 300 CU3A 35Vitocrossal 300 CU3A 45Vitocrossal 300 CU3A 57Vitocrossal 300 CU3A 94Vitocrossal 300 CU3A 125Vitocrossal 300 CU3A 160Vitocrossal 300 CU3A 199
Source: Vitocrossal 300 CU3A application guide, p. 50-52. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.