Viessmann Boiler: Adjusting the adjustable high limit to 100 °C / 212 °F
Adjusting the adjustable high limit to 100 °C / 212 °F on a Viessmann boiler: Changes the adjustable high limit from the factory 95 °C / 203 °F. Limit the DHW temperature when the system feeds a DHW tank.
Applies to: Vitotronic 100 GC1 adjustable high limit
How to fix adjusting the adjustable high limit to 100 °c / 212 °f: step by step
- Disconnect power to the control and burner.
- Using a suitable screwdriver, lever out and remove selector knob R behind the hinged cover.
- With pointed pliers, break off the cams shaded in the figure from the stop dial.
- Refit selector knob R so the marking sits in the centre of the selected range.
- Note the coding address 06 setting.
If the unit shows an error code, look it up: Viessmann Boiler codes
Source: Vitotronic 100 GC1 installation and service instructions, p. 48. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.