Viessmann Boiler: Adjust the heating curve for a heating circuit
Adjust the heating curve for a heating circuit on a Viessmann boiler: Set slope and shift so the supply temperature follows the outside temperature for the system type. Factory slope is 1.4 and shift is 0. Underfloor systems are about slope 0.2 to 0.8, low temperature systems about 0.8 to 1.6, and systems above 167°F (75°C) boiler water are above 1.6.
Applies to: Vitocrossal 200 CI2 heating circuits
How to fix adjust the heating curve for a heating circuit: step by step
- Tap the menu button and select Heating.
- Select the required heating circuit.
- Select Heating curve.
- Set Slope and Shift with the +/- keys.
- Confirm the entry.
If the unit shows an error code, look it up: Viessmann Boiler codes
Models
399500750100015002000CI2 399CI2 399/500CI2 500CI2 750CI2 750/1000CI2 1000CI2 1500CI2 1500/2000CI2 2000Vitocrossal 200 CI2 399Vitocrossal 200 CI2 500Vitocrossal 200 CI2 750Vitocrossal 200 CI2 1000Vitocrossal 200 CI2 1500Vitocrossal 200 CI2 2000
Source: Vitocrossal 200 CI2 service instructions, p. 17-18. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.