Viessmann Boiler: Adjust CO2 at full load
Adjust CO2 at full load on a Viessmann boiler: Adjusts the CO2 level at upper heating input.
Applies to: Vitocrossal 300 CA3B Dual Fuel burner
How to fix adjust co2 at full load: step by step
- Set the service display to 100 (100%) for upper heating input.
- Check the CO2 level at the flue pipe.
- If the CO2 is out of range, remove cap B and turn adjusting screw A in small steps with a 3 mm Allen key.
- Turning clockwise lowers CO2 (less gas). Turning counter-clockwise raises CO2 (more gas).
- Record the reading in the maintenance report on page 158.
If the unit shows an error code, look it up: Viessmann Boiler codes
More service & test modes tips for boiler
Source: Vitocrossal 300 CA3B Dual Fuel Series 2.5 to 6.0 Service Instructions, p. 66. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.