Viessmann Boiler: Access the burner and disconnect the burner control
Access the burner and disconnect the burner control on a Viessmann boiler: Preparation steps before working on the burner.
Applies to: Burner control and burner door
How to fix access the burner and disconnect the burner control: step by step
- Close the main gas supply valve.
- Switch off the main power switch and confirm power is off.
- Remove the front panel and side panels per the boiler installation instructions.
- Remove plugs 41 and 90 from the burner control and plugs 40/156, 40 and 53 from the burner bracket.
- Remove plugs from the electrodes.
- Remove the air intake adaptor and air flex hose.
- Open the gas connection to the burner.
- Loosen the four M12 bolts and open the burner door.
- Loosen the two programming unit screws, lift the unit off and disconnect its cable.
- Disconnect all cables from the burner control sub-base.
If the unit shows an error code, look it up: Viessmann Boiler codes
Models
186246311CM2 186 burnerCM2 246 burnerCM2 311 burnerVitocrossal 200 CM2 186Vitocrossal 200 CM2 246Vitocrossal 200 CM2 311Vitocrossal 200 CM2 400Vitocrossal 200 CM2 500Vitocrossal 200 CM2 620Vitocrossal 200 CM2 620 TX
Source: Vitocrossal 200 CM2 186 to 311 service instructions, p. 30. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.