Viessmann Heat Pump: Power and communication wiring between units
Power and communication wiring between units on a Viessmann heat pump: Size wires per NEC or CEC and local codes, using the MCA and MOP values from the electrical data table to size the wires and the disconnect fuse or breaker. Power and communication run as 14/3 field wire: two high-voltage AC wires, one communication wire and one ground. The wiring is polarity sensitive. BX cable is not recommended. In high EMF areas with communication problems, 14/2 stranded shielded wire can replace L2 and S, with the shield grounded at the outdoor unit only. Power is a single-point connection to the outdoor unit.
Applies to: All D5CSRA systems
How to fix power and communication wiring between units: step by step
- Size wires and the disconnect using the MCA and MOP values.
- Run 14/3 power and communication wire with two AC wires, one communication wire and one ground.
- Keep polarity correct between indoor and outdoor units.
- Do not use BX cable.
- In high EMF areas, use 14/2 stranded shielded wire and ground the shield at the outdoor unit only.
If the unit shows an error code, look it up: Viessmann Heat Pump codes
Source: Carrier D5CSRA Product Data, p. 188. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.