Carrier Heat Pump: Triple evacuation method (when the pump cannot reach 500 micron)
Triple evacuation method (when the pump cannot reach 500 micron) on a Carrier heat pump: Use only if the vacuum pump cannot pull 500 micron and the system holds no liquid water. Always break vacuum with dry nitrogen.
Applies to: D5CURA evacuation when deep vacuum is not possible
How to fix triple evacuation method (when the pump cannot reach 500 micron): step by step
- Attach gauges and evacuate the system to 28 in Hg. Keep the pump running for 15 more minutes.
- Close the service valves and shut off the pump.
- Connect a nitrogen cylinder with regulator and flow nitrogen until system pressure reads 2 psig.
- Close the service valve and let the system stand for 1 hour so the dry nitrogen can absorb moisture.
- Repeat the evacuation and nitrogen steps as shown in Fig. 20 until the system is clean and dry.
If the unit shows an error code, look it up: Carrier Heat Pump codes
Models
D5CURA + D5MUWAD5CURAH18AAKD5CURAH24AAKD5CURAH30AAKD5CURAH36AAKD5CURAH48AAKD5CURAH60AAK
More commissioning tips for heat pump
Source: D5CURA service manual, p. 21. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.