Carrier Heat Pump: Routing the connecting pipe between units
Routing the connecting pipe between units on a Carrier heat pump: Keep the refrigerant line within limits and stop water getting into the indoor unit.
Applies to: Field refrigerant piping
Common causes of routing the connecting pipe between units
- Rain running down the line can enter the indoor unit.
- Buried pipe that is too long lets refrigerant migrate, causing slugging at start-up.
How to fix routing the connecting pipe between units: step by step
- Check the height difference and total length against Table 6.
- If the outdoor unit is higher than the indoor unit, make a downward arc in the pipe before it enters the wall so rain drips off first.
- Do not bury more than 36 in (914 mm) of refrigerant pipe. If any is buried, give it a 6 in (152 mm) vertical rise to the outdoor valve connections.
- Do not install the connecting pipe until both the indoor and outdoor units are in place.
If the unit shows an error code, look it up: Carrier Heat Pump codes
Models
D5CURA + D5MUWAD5CURAH18AAKD5CURAH24AAKD5CURAH30AAKD5CURAH36AAKD5CURAH48AAKD5CURAH60AAK
Source: Carrier D5CURA installation manual, p. 8 and p. 13. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.