Carrier Heat Pump: Refrigerant line routing and insulation rules
Refrigerant line routing and insulation rules on a Carrier heat pump: Keep buried line length and drop height within limits, insulate the suction line, and isolate the tubing from the building structure.
Applies to: D5CURA refrigerant piping
How to fix refrigerant line routing and insulation rules: step by step
- Do not bury more than 36 in (914 mm) of refrigerant pipe.
- If any pipe is buried, provide at least a 6 in (152 mm) vertical rise to the outdoor unit service valves to prevent refrigerant migration and slugging at start-up.
- Insulate the suction line with at least 1/2 in (12.7 mm) thick insulation. Closed-cell insulation is recommended on long-line runs.
- Isolate the interconnecting tubing from the building structure so vibration and noise do not transmit into it.
If the unit shows an error code, look it up: Carrier Heat Pump codes
Models
D5CURA + D5MUWAD5CURAH18AAKD5CURAH24AAKD5CURAH30AAKD5CURAH36AAKD5CURAH48AAKD5CURAH60AAK
More commissioning tips for heat pump
Source: D5CURA service manual, p. 20. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.